SIL2, Cat.3/PL d
No. The line module should be disabled when all axes have stopped moving. This allows for the line module to regenerate any excess energy that is produced by the motors stopping. A typical example would be to use a delayed safety contact to disable the module after the SS1 delay time has expired.
Communication from a master device is partially or yet to be fully established. Therefore, cyclic communication is not possible.
Go to “Drive” -> ”Diagnostics” -> ”Alarms history”
For a non-DRIVE-CLiQ line module (power rating less than 16kw): You must connect Pin 1 of the X21 connector to a digital input on your control unit. You must then set p864 from the expert list of each drive object to read the specified digital input. So p864 = Control_Unit.r722.X.
For DRIVE-CLiQ line modules (power rating of 16kW or above), the unit can be enabled either from a SIMOTION unit, or via PLC:
SIMOTION: Use the system function block _LineModule_Control. For a detailed explanation of this function block, see https://support.industry.siemens.com/cs/document/1...
PLC: Use the SINA_INFEED function block from the DriveLib library in TIA Portal V14 onwards. The DriveLib library can be found at https://support.industry.siemens.com/cs/document/1... if not already installed. Documentation on the use of this function block can also be found here.
Navigate to the top toolbar:
“View”->” Toolbars”. Removing the tick from the boxes will remove the shortcut buttons from the toolbar.
Yes. Press Shift + F1 then click on the desired parameter. If the help section of the software has been installed, then contextual help on that parameter will be displayed.
On the top toolbar navigate to: “Help”->” Installed devices…”.
OFF enables are the three main enables that exist in the drive. By individually removing them they are differentiated in the following way:
In the drive expert list set the following parameters in the order prescribed:
The brake can be released by one of the following methods:
The drive uses parameters p2000-p2007 to reference any relative values that are specified within the expert list. These parameter values represent 100% of their specified units. Values of 4000 hex for an integer or 40000000 hex for a double integer are used to represent 100% when actual values i.e. speed, are passed in a telegram.
Yes. In the “Measurement” tab in the trace window right click on one of the recorded traces. Select “Export measurements”, create a filename and choose a storage location. Select the desired traces for export and click “OK”.
There is an error with the communication setting between the drive and PLC. This could be caused by:
Several issues could be the cause of this. A few typical causes are listed below:
- Communication cable is unplugged/damaged.
- Drive is in a boot up state.
- Flash card is unplugged.
- Installed hardware revisions are not correct.
PG/PC
- Programming device has not been assigned in NetPro.
- Correct communication path, Device/S7ONLINE, has not been selected.
- Incorrect communication protocol has been set.
Profinet
- IP address on the programming device is not set to the range of the drive or is the same address.
- Using an eWON connection. Profibus
- Baud rate is set incorrectly.
- Node address on the programming device is the same as the drive.
- “PG/PC is the only master on the bus” is/is not set. This is specific for direct connection to a drive or via a routing method.
The most common cause of this is attempting to get onlie to the device via an ethernet/profinet port other than that which is specified in the project.
Several issues could be the cause of this. A few typical causes are listed below:
- Communication cable is unplugged/damaged.
- Drive is in a boot up state.
- Flash card is unplugged.
- Installed hardware revisions are not correct.
PG/PC
- Programming device has not been assigned in NetPro.
- Correct communication path, Device/S7ONLINE, has not been selected.
- Incorrect communication protocol has been set.
Profinet
- IP address on the programming device is not set to the range of the drive or is the same address.
- Using an eWON connection. Profibus
- Baud rate is set incorrectly.
- Node address on the programming device is the same as the drive.
- “PG/PC is the only master on the bus” is/is not set. This is specific for direct connection to a drive or via a routing method.
Important basic DRIVE-CLiQ wiring principles are listed below:
The EP terminals only need to be wired when the Safety Integrated configuration in the drive is set to use “terminal”. So, if Profisafe or a TM54F is used, the EP terminals are not needed.