In the drive expert list set the following parameters in the order prescribed:
1. p10 = [3]
2. p1821 = CW or CCW
3. p10 = [0]
Setting p1821 to CW (Clockwise) or CCW (Counter Clockwise) will change the positive direction of rotation. Positive direction is considered when looking at the motor shaft.