Important basic DRIVE-CLiQ wiring principles are listed below:

- Ring topology is not allowed
- Devices with the same bus speed can be daisy chained together.
- Servo and vector drives must have separate connections.
- TM modules must have own connection.
- Line modules will have own connection.
- VSM will be connected to the Line module. 